    "dataType": "CVE_RECORD",
    "dataVersion": "5.1",
    "cveMetadata": {
        "cveId": "CVE-2024-2425",
        "assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0",
        "state": "PUBLISHED",
        "assignerShortName": "Rockwell",
        "dateReserved": "2024-03-13T14:45:09.065Z",
        "datePublished": "2024-03-25T20:14:01.767Z",
        "dateUpdated": "2024-08-01T19:11:53.614Z"
    },
    "containers": {
        "cna": {
            "affected": [
                {
                    "defaultStatus": "unaffected",
                    "product": "PowerFlex® 527",
                    "vendor": "Rockwell Automation ",
                    "versions": [
                        {
                            "status": "affected",
                            "version": " v2.001.x <"
                        }
                    ]
                }
            ],
            "datePublic": "2024-03-21T13:00:00.000Z",
            "descriptions": [
                {
                    "lang": "en",
                    "supportingMedia": [
                        {
                            "base64": false,
                            "type": "text/html",
                            "value": "\n\n<span style=\"background-color: rgb(255, 255, 255);\">A denial-of-service vulnerability exists in the Rockwell Automation PowerFlex® 527 due to improper input validation in the device. If exploited, the web server will crash and need a manual restart to recover it.</span>\n\n"
                        }
                    ],
                    "value": "\nA denial-of-service vulnerability exists in the Rockwell Automation PowerFlex® 527 due to improper input validation in the device. If exploited, the web server will crash and need a manual restart to recover it.\n\n"
                }
            ],
            "impacts": [
                {
                    "capecId": "CAPEC-153",
                    "descriptions": [
                        {
                            "lang": "en",
                            "value": "CAPEC-153 Input Data Manipulation"
                        }
                    ]
                }
            ],
            "metrics": [
                {
                    "cvssV3_1": {
                        "attackComplexity": "LOW",
                        "attackVector": "NETWORK",
                        "availabilityImpact": "HIGH",
                        "baseScore": 7.5,
                        "baseSeverity": "HIGH",
                        "confidentialityImpact": "NONE",
                        "integrityImpact": "NONE",
                        "privilegesRequired": "NONE",
                        "scope": "UNCHANGED",
                        "userInteraction": "NONE",
                        "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
                        "version": "3.1"
                    },
                    "format": "CVSS",
                    "scenarios": [
                        {
                            "lang": "en",
                            "value": "GENERAL"
                        }
                    ]
                }
            ],
            "problemTypes": [
                {
                    "descriptions": [
                        {
                            "cweId": "CWE-20",
                            "description": "CWE-20 Improper Input Validation",
                            "lang": "en",
                            "type": "CWE"
                        }
                    ]
                }
            ],
            "providerMetadata": {
                "orgId": "b73dd486-f505-4403-b634-40b078b177f0",
                "shortName": "Rockwell",
                "dateUpdated": "2024-03-25T20:18:14.816Z"
            },
            "references": [
                {
                    "url": "https://https://www.rockwellautomation.com/en-us/support/advisory.SD1664.html"
                }
            ],
            "solutions": [
                {
                    "lang": "en",
                    "supportingMedia": [
                        {
                            "base64": false,
                            "type": "text/html",
                            "value": "\n\n<p>There is no fix currently for this vulnerability. Users using the affected software are encouraged to apply risk mitigations and security best practices, where possible.</p><ul><li>Implement network segmentation confirming the device is on an isolated network.</li><li><a target=\"_blank\" rel=\"nofollow\" href=\"https://literature.rockwellautomation.com/idc/groups/literature/documents/um/520-um002_-en-e.pdf\">Disable the web server</a>, if not needed. The web server is disabled by default. Disabling this feature is available in v2.001.x and later.</li><li><a target=\"_blank\" rel=\"nofollow\" href=\"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight\">Security Best Practices</a></li></ul>"
                        }
                    ],
                    "value": "\nThere is no fix currently for this vulnerability. Users using the affected software are encouraged to apply risk mitigations and security best practices, where possible.\n\n  *  Implement network segmentation confirming the device is on an isolated network.\n  *   Disable the web server https://literature.rockwellautomation.com/idc/groups/literature/documents/um/520-um002_-en-e.pdf , if not needed. The web server is disabled by default. Disabling this feature is available in v2.001.x and later.\n  *   Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight \n\n"
                }
            ],
            "source": {
                "discovery": "INTERNAL"
            },
            "title": "Rockwell Automation - Denial-of-service and Input Validation Vulnerabilities in PowerFlex® 527",
            "x_generator": {
                "engine": "Vulnogram 0.1.0-dev"
            }
        },
        "adp": [
            {
                "title": "CISA ADP Vulnrichment",
                "metrics": [
                    {
                        "other": {
                            "type": "ssvc",
                            "content": {
                                "id": "CVE-2024-2425",
                                "role": "CISA Coordinator",
                                "options": [
                                    {
                                        "Exploitation": "none"
                                    },
                                    {
                                        "Automatable": "no"
                                    },
                                    {
                                        "Technical Impact": "partial"
                                    }
                                ],
                                "version": "2.0.3",
                                "timestamp": "2024-03-28T18:27:55.373294Z"
                            }
                        }
                    }
                ],
                "providerMetadata": {
                    "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
                    "shortName": "CISA-ADP",
                    "dateUpdated": "2024-06-04T17:30:25.436Z"
                }
            },
            {
                "providerMetadata": {
                    "orgId": "af854a3a-2127-422b-91ae-364da2661108",
                    "shortName": "CVE",
                    "dateUpdated": "2024-08-01T19:11:53.614Z"
                },
                "title": "CVE Program Container",
                "references": [
                    {
                        "url": "https://https://www.rockwellautomation.com/en-us/support/advisory.SD1664.html",
                        "tags": [
                            "x_transferred"
                        ]
                    }
                ]
            }
        ]
    }
}