    "dataType": "CVE_RECORD",
    "dataVersion": "5.1",
    "cveMetadata": {
        "cveId": "CVE-2023-46102",
        "assignerOrgId": "c95f66b2-7e7c-41c5-8f09-6f86ec68659c",
        "state": "PUBLISHED",
        "assignerShortName": "bosch",
        "dateReserved": "2023-10-18T09:35:22.530Z",
        "datePublished": "2023-10-25T14:19:20.107Z",
        "dateUpdated": "2024-09-11T13:49:04.787Z"
    },
    "containers": {
        "cna": {
            "providerMetadata": {
                "orgId": "c95f66b2-7e7c-41c5-8f09-6f86ec68659c",
                "shortName": "bosch",
                "dateUpdated": "2023-10-25T14:19:20.107Z"
            },
            "descriptions": [
                {
                    "lang": "en",
                    "value": "The Android Client application, when enrolled to the AppHub server, connects to an MQTT\r\nbroker to exchange messages and receive commands to execute on the HMI device.\r\nThe protocol builds on top of MQTT to implement the remote management of the device is encrypted with a hard-coded DES symmetric key, that can be retrieved reversing both the Android Client application and the server-side web application.\r\n\r\n\r\nThis issue allows an attacker able to control a malicious MQTT broker on the same subnet\r\nnetwork of the device, to craft malicious messages and send them to the HMI device, executing arbitrary commands on the device itself."
                }
            ],
            "affected": [
                {
                    "vendor": "Bosch Rexroth AG",
                    "product": "ctrlX HMI Web Panel - WR21 (WR2107)",
                    "versions": [
                        {
                            "version": "all",
                            "status": "affected"
                        }
                    ]
                },
                {
                    "vendor": "Bosch Rexroth AG",
                    "product": "ctrlX HMI Web Panel - WR21 (WR2110)",
                    "versions": [
                        {
                            "version": "all",
                            "status": "affected"
                        }
                    ]
                },
                {
                    "vendor": "Bosch Rexroth AG",
                    "product": "ctrlX HMI Web Panel - WR21 (WR2115)",
                    "versions": [
                        {
                            "version": "all",
                            "status": "affected"
                        }
                    ]
                }
            ],
            "problemTypes": [
                {
                    "descriptions": [
                        {
                            "lang": "en-US",
                            "description": "CWE-798 Use of Hard-coded Credentials",
                            "cweId": "CWE-798"
                        }
                    ]
                }
            ],
            "references": [
                {
                    "url": "https://psirt.bosch.com/security-advisories/BOSCH-SA-175607.html",
                    "name": "https://psirt.bosch.com/security-advisories/BOSCH-SA-175607.html",
                    "tags": [
                        "vendor-advisory"
                    ]
                }
            ],
            "metrics": [
                {
                    "cvssV3_1": {
                        "version": "3.1",
                        "vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
                        "attackVector": "ADJACENT_NETWORK",
                        "attackComplexity": "LOW",
                        "privilegesRequired": "NONE",
                        "userInteraction": "NONE",
                        "scope": "UNCHANGED",
                        "confidentialityImpact": "HIGH",
                        "integrityImpact": "HIGH",
                        "availabilityImpact": "HIGH",
                        "baseScore": 8.8,
                        "baseSeverity": "HIGH"
                    }
                }
            ]
        },
        "adp": [
            {
                "providerMetadata": {
                    "orgId": "af854a3a-2127-422b-91ae-364da2661108",
                    "shortName": "CVE",
                    "dateUpdated": "2024-08-02T20:37:39.622Z"
                },
                "title": "CVE Program Container",
                "references": [
                    {
                        "url": "https://psirt.bosch.com/security-advisories/BOSCH-SA-175607.html",
                        "name": "https://psirt.bosch.com/security-advisories/BOSCH-SA-175607.html",
                        "tags": [
                            "vendor-advisory",
                            "x_transferred"
                        ]
                    }
                ]
            },
            {
                "affected": [
                    {
                        "vendor": "boschrexrothag",
                        "product": "ctrl_hmi_web_panel-wr21_\\(wr2110\\)",
                        "cpes": [
                            "cpe:2.3:a:boschrexrothag:ctrl_hmi_web_panel-wr21_\\(wr2110\\):*:*:*:*:*:*:*:*"
                        ],
                        "defaultStatus": "unknown",
                        "versions": [
                            {
                                "version": "0",
                                "status": "affected",
                                "lessThan": "*",
                                "versionType": "custom"
                            }
                        ]
                    },
                    {
                        "vendor": "boschrexrothag",
                        "product": "ctrl_hmi_web_panel-wr21_\\(wr2115\\)",
                        "cpes": [
                            "cpe:2.3:a:boschrexrothag:ctrl_hmi_web_panel-wr21_\\(wr2115\\):*:*:*:*:*:*:*:*"
                        ],
                        "defaultStatus": "unknown",
                        "versions": [
                            {
                                "version": "0",
                                "status": "affected",
                                "lessThan": "*",
                                "versionType": "custom"
                            }
                        ]
                    },
                    {
                        "vendor": "boschrexrothag",
                        "product": "ctrl_hmi_web_panel-wr21_\\(wr2107\\)",
                        "cpes": [
                            "cpe:2.3:a:boschrexrothag:ctrl_hmi_web_panel-wr21_\\(wr2107\\):*:*:*:*:*:*:*:*"
                        ],
                        "defaultStatus": "unknown",
                        "versions": [
                            {
                                "version": "0",
                                "status": "affected",
                                "lessThan": "*",
                                "versionType": "custom"
                            }
                        ]
                    }
                ],
                "metrics": [
                    {
                        "other": {
                            "type": "ssvc",
                            "content": {
                                "timestamp": "2024-09-11T13:45:20.593751Z",
                                "id": "CVE-2023-46102",
                                "options": [
                                    {
                                        "Exploitation": "none"
                                    },
                                    {
                                        "Automatable": "no"
                                    },
                                    {
                                        "Technical Impact": "total"
                                    }
                                ],
                                "role": "CISA Coordinator",
                                "version": "2.0.3"
                            }
                        }
                    }
                ],
                "title": "CISA ADP Vulnrichment",
                "providerMetadata": {
                    "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
                    "shortName": "CISA-ADP",
                    "dateUpdated": "2024-09-11T13:49:04.787Z"
                }
            }
        ]
    }
}