    "dataType": "CVE_RECORD",
    "dataVersion": "5.1",
    "cveMetadata": {
        "cveId": "CVE-2022-3192",
        "assignerOrgId": "2b718523-d88f-4f37-9bbd-300c20644bf9",
        "state": "PUBLISHED",
        "assignerShortName": "ABB",
        "dateReserved": "2022-09-13T05:57:45.421Z",
        "datePublished": "2023-03-31T16:13:13.149Z",
        "dateUpdated": "2024-08-03T01:00:10.643Z"
    },
    "containers": {
        "cna": {
            "affected": [
                {
                    "collectionURL": "https://abb.com/plc",
                    "defaultStatus": "unknown",
                    "packageName": "PM5xx",
                    "product": "AC500 V2",
                    "vendor": "ABB",
                    "versions": [
                        {
                            "lessThan": "2.8.6",
                            "status": "affected",
                            "version": "2.0.0",
                            "versionType": "release"
                        }
                    ]
                }
            ],
            "credits": [
                {
                    "lang": "en",
                    "type": "finder",
                    "user": "00000000-0000-4000-9000-000000000000",
                    "value": "ABB thanks the following for working with us to help protect customers:  CVE-2022-3192: Parul Sindhwad and Dr. Faruk Kazi of CoE CNDS lab, VJTI, Mumbai (India) for reporting this vulnerability following coordinated disclosure."
                }
            ],
            "descriptions": [
                {
                    "lang": "en",
                    "supportingMedia": [
                        {
                            "base64": false,
                            "type": "text/html",
                            "value": "Improper Input Validation vulnerability in ABB AC500 V2 PM5xx allows Client-Server Protocol Manipulation.<p>This issue affects AC500 V2: from 2.0.0 before 2.8.6.</p>"
                        }
                    ],
                    "value": "Improper Input Validation vulnerability in ABB AC500 V2 PM5xx allows Client-Server Protocol Manipulation.This issue affects AC500 V2: from 2.0.0 before 2.8.6.\n\n"
                }
            ],
            "impacts": [
                {
                    "capecId": "CAPEC-220",
                    "descriptions": [
                        {
                            "lang": "en",
                            "value": "CAPEC-220 Client-Server Protocol Manipulation"
                        }
                    ]
                }
            ],
            "metrics": [
                {
                    "cvssV3_1": {
                        "attackComplexity": "LOW",
                        "attackVector": "NETWORK",
                        "availabilityImpact": "LOW",
                        "baseScore": 5.3,
                        "baseSeverity": "MEDIUM",
                        "confidentialityImpact": "NONE",
                        "integrityImpact": "NONE",
                        "privilegesRequired": "NONE",
                        "scope": "UNCHANGED",
                        "userInteraction": "NONE",
                        "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L",
                        "version": "3.1"
                    },
                    "format": "CVSS",
                    "scenarios": [
                        {
                            "lang": "en",
                            "value": "GENERAL"
                        }
                    ]
                }
            ],
            "problemTypes": [
                {
                    "descriptions": [
                        {
                            "cweId": "CWE-754",
                            "description": "CWE-754 Improper Check for Unusual or Exceptional Conditions",
                            "lang": "en",
                            "type": "CWE"
                        }
                    ]
                }
            ],
            "providerMetadata": {
                "orgId": "2b718523-d88f-4f37-9bbd-300c20644bf9",
                "shortName": "ABB",
                "dateUpdated": "2023-09-13T03:57:46.530Z"
            },
            "references": [
                {
                    "url": "https://search.abb.com/library/Download.aspx?DocumentID=3ADR011162&LanguageCode=en&DocumentPartId=&Action=Launch"
                }
            ],
            "source": {
                "discovery": "EXTERNAL"
            },
            "title": " Improper Check for Unusual or Exceptional Conditions",
            "workarounds": [
                {
                    "lang": "en",
                    "supportingMedia": [
                        {
                            "base64": false,
                            "type": "text/html",
                            "value": "<div>Use the communication protocol \"Tcp/Ip\" instead of \"ABB Tcp/Ip Level 2\" (i.e. Port 1201 instead of 1200) for the connection between engineering software and PLC. <br></div><div>This protocol/port is not affected by the DoS impact of the vulnerability.<br></div>"
                        }
                    ],
                    "value": "Use the communication protocol \"Tcp/Ip\" instead of \"ABB Tcp/Ip Level 2\" (i.e. Port 1201 instead of 1200) for the connection between engineering software and PLC. \n\n\nThis protocol/port is not affected by the DoS impact of the vulnerability.\n\n\n"
                }
            ],
            "x_generator": {
                "engine": "Vulnogram 0.1.0-dev"
            }
        },
        "adp": [
            {
                "providerMetadata": {
                    "orgId": "af854a3a-2127-422b-91ae-364da2661108",
                    "shortName": "CVE",
                    "dateUpdated": "2024-08-03T01:00:10.643Z"
                },
                "title": "CVE Program Container",
                "references": [
                    {
                        "url": "https://search.abb.com/library/Download.aspx?DocumentID=3ADR011162&LanguageCode=en&DocumentPartId=&Action=Launch",
                        "tags": [
                            "x_transferred"
                        ]
                    }
                ]
            }
        ]
    }
}