    "data_version": "4.0",
    "data_type": "CVE",
    "data_format": "MITRE",
    "CVE_data_meta": {
        "ID": "CVE-2024-3493",
        "ASSIGNER": "PSIRT@rockwellautomation.com",
        "STATE": "PUBLIC"
    },
    "description": {
        "description_data": [
            {
                "lang": "eng",
                "value": "\nA specific malformed fragmented packet type (fragmented packets may be generated automatically by devices that send large amounts of data) can cause a major nonrecoverable fault (MNRF) Rockwell Automation's ControlLogix 5580, Guard Logix\u00a05580,\u00a0CompactLogix 5380,\u00a0and 1756-EN4TR. If exploited, the affected product will become unavailable and require a manual restart to recover it. Additionally, an MNRF could result in a loss of view and/or control of connected devices. \n\n"
            }
        ]
    },
    "problemtype": {
        "problemtype_data": [
            {
                "description": [
                    {
                        "lang": "eng",
                        "value": "CWE-20 Improper Input Validation",
                        "cweId": "CWE-20"
                    }
                ]
            }
        ]
    },
    "affects": {
        "vendor": {
            "vendor_data": [
                {
                    "vendor_name": "Rockwell Automation",
                    "product": {
                        "product_data": [
                            {
                                "product_name": "ControlLogix 5580",
                                "version": {
                                    "version_data": [
                                        {
                                            "version_affected": "=",
                                            "version_value": "v35.011"
                                        }
                                    ]
                                }
                            },
                            {
                                "product_name": "GuardLogix 5580",
                                "version": {
                                    "version_data": [
                                        {
                                            "version_affected": "=",
                                            "version_value": "v35.011"
                                        }
                                    ]
                                }
                            },
                            {
                                "product_name": "CompactLogix 5380",
                                "version": {
                                    "version_data": [
                                        {
                                            "version_affected": "=",
                                            "version_value": "v5.001"
                                        }
                                    ]
                                }
                            },
                            {
                                "product_name": "1756-EN4TR",
                                "version": {
                                    "version_data": [
                                        {
                                            "version_affected": "=",
                                            "version_value": "v5.001"
                                        }
                                    ]
                                }
                            }
                        ]
                    }
                }
            ]
        }
    },
    "references": {
        "reference_data": [
            {
                "url": "https://www.rockwellautomation.com/en-us/support/advisory.SD1666.html",
                "refsource": "MISC",
                "name": "https://www.rockwellautomation.com/en-us/support/advisory.SD1666.html"
            }
        ]
    },
    "generator": {
        "engine": "Vulnogram 0.1.0-dev"
    },
    "source": {
        "discovery": "INTERNAL"
    },
    "solution": [
        {
            "lang": "en",
            "supportingMedia": [
                {
                    "base64": false,
                    "type": "text/html",
                    "value": "\n\n<p>\n\n</p><table><tbody><tr><td><p><br>Affected Product</p><p>&nbsp;</p><p>&nbsp;</p></td><td><p>&nbsp;</p><p>&nbsp;</p><p>First Known in Firmware Revision</p><p>&nbsp;</p><p>&nbsp;</p></td><td><p>&nbsp;</p><p>&nbsp;</p><p>Corrected in Firmware Revision</p><p>&nbsp;</p><p>&nbsp;</p></td></tr><tr><td><p>&nbsp;</p><p>&nbsp;</p><p>ControlLogix\u00ae 5580</p><p>&nbsp;</p><p>&nbsp;</p></td><td><p>&nbsp;</p><p>&nbsp;</p><p>V35.011</p><p>&nbsp;</p><p>&nbsp;</p></td><td><p>&nbsp;</p><p>&nbsp;</p><p>V35.013, V36.011</p><p>&nbsp;</p><p>&nbsp;</p></td></tr><tr><td><p>&nbsp;</p><p>&nbsp;</p><p>GuardLogix 5580</p><p>&nbsp;</p><p>&nbsp;</p></td><td><p>&nbsp;</p><p>&nbsp;</p><p>V35.011</p><p>&nbsp;</p><p>&nbsp;</p></td><td><p>&nbsp;</p><p>&nbsp;</p><p>V35.013, V36.011</p><p>&nbsp;</p><p>&nbsp;</p></td></tr><tr><td><p>&nbsp;</p><p>&nbsp;</p><p>CompactLogix 5380</p><p>&nbsp;</p><p>&nbsp;</p></td><td><p>&nbsp;</p><p>&nbsp;</p><p>V35.011</p><p>&nbsp;</p><p>&nbsp;</p></td><td><p>&nbsp;</p><p>&nbsp;</p><p>V35.013, V36.011</p><p>&nbsp;</p><p>&nbsp;</p></td></tr><tr><td><p>&nbsp;</p><p>&nbsp;</p><p>1756-EN4TR</p><p>&nbsp;</p><p>&nbsp;</p></td><td><p>&nbsp;</p><p>&nbsp;</p><p>V5.001</p><p>&nbsp;</p><p>&nbsp;</p></td><td><p>&nbsp;</p><p>&nbsp;</p><p>V6.001</p><p>&nbsp;</p><p>&nbsp;</p></td></tr></tbody></table>\n\n<br><br><p></p><p>Users using the affected software and who are not able to upgrade to one of the corrected versions are encouraged to apply security best practices, where possible.\u202f\u202f</p><ul><li><p><a target=\"_blank\" rel=\"nofollow\" href=\"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight\">Security Best Practices</a>&nbsp;</p></li></ul>\n\n<br>"
                }
            ],
            "value": "\nAffected Product\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nFirst Known in Firmware Revision\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nCorrected in Firmware Revision\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nControlLogix\u00ae 5580\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.013, V36.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nGuardLogix 5580\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.013, V36.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nCompactLogix 5380\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV35.013, V36.011\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n1756-EN4TR\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV5.001\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\n\u00a0\n\nV6.001\n\n\u00a0\n\n\u00a0\n\nUsers using the affected software and who are not able to upgrade to one of the corrected versions are encouraged to apply security best practices, where possible.\u202f\u202f\n\n  *   Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight \u00a0\n\n"
        }
    ],
    "impact": {
        "cvss": [
            {
                "attackComplexity": "LOW",
                "attackVector": "NETWORK",
                "availabilityImpact": "HIGH",
                "baseScore": 8.6,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "NONE",
                "integrityImpact": "NONE",
                "privilegesRequired": "NONE",
                "scope": "CHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H",
                "version": "3.1"
            }
        ]
    }
}