    "CVE_data_meta": {
        "ASSIGNER": "cve@mitre.org",
        "ID": "CVE-2022-30319",
        "STATE": "PUBLIC"
    },
    "affects": {
        "vendor": {
            "vendor_data": [
                {
                    "product": {
                        "product_data": [
                            {
                                "product_name": "n/a",
                                "version": {
                                    "version_data": [
                                        {
                                            "version_value": "n/a"
                                        }
                                    ]
                                }
                            }
                        ]
                    },
                    "vendor_name": "n/a"
                }
            ]
        }
    },
    "data_format": "MITRE",
    "data_type": "CVE",
    "data_version": "4.0",
    "description": {
        "description_data": [
            {
                "lang": "eng",
                "value": "Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration."
            }
        ]
    },
    "problemtype": {
        "problemtype_data": [
            {
                "description": [
                    {
                        "lang": "eng",
                        "value": "n/a"
                    }
                ]
            }
        ]
    },
    "references": {
        "reference_data": [
            {
                "url": "https://www.forescout.com/blog/",
                "refsource": "MISC",
                "name": "https://www.forescout.com/blog/"
            },
            {
                "refsource": "MISC",
                "name": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-03",
                "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-03"
            }
        ]
    }
}